Push-On Multipurpose Hose
Textile-braided multipurpose push-on hose for selected low-pressure air, water and fluid services, kept separate from the EPDM data-centre cooling range.

An oil-resistant tube, textile braid and oil- and weather-resistant synthetic-rubber cover serve selected utility-transfer applications. Choose the tube compound and fitting system for the fluid; this hose is not an automatic substitute for dedicated EPDM coolant hose.
Product views
Multipurpose hose tube, braid and cover
Technical overview
Construction and service distinction
An oil-resistant rubber tube, textile braid and synthetic-rubber cover suit selected low-pressure hydraulic, air, water, water-glycol, antifreeze, fuel and lubricating-oil applications. Confirm compatibility with the actual fluid, temperature and fitting system.
Medium-specific temperature limits
The general range is −40°C to +100°C. The stated exceptions are air up to +70°C and water up to +85°C. Do not apply the general upper limit to those services or to a finished assembly without confirmation.
Pressure and assembly requirements
Confirm the applicable SAE 100R6 revision, burst and impulse requirements, temperature derating and test evidence. Verify whether the vacuum figures use gauge or absolute pressure before vacuum service.
Specifications
| DN | Size (in) | Dash size | ID (mm) | OD (mm) | Maximum working pressure (psi / MPa) | Minimum bend radius (mm) | Mass (kg/m) | Vacuum pressure (kPa; basis unspecified) |
|---|---|---|---|---|---|---|---|---|
| 6 | 1/4 | -4 | 6.3 | 12.7 | 350 / 2.4 | 65 | 0.13 | 95 |
| 10 | 3/8 | -6 | 9.5 | 15.9 | 350 / 2.4 | 75 | 0.16 | 95 |
| 12 | 1/2 | -8 | 12.7 | 19.8 | 300 / 2.1 | 125 | 0.27 | 95 |
| 16 | 5/8 | -10 | 15.9 | 23.0 | 300 / 2.1 | 150 | 0.28 | 51 |
| 20 | 3/4 | -12 | 19.1 | 26.2 | 300 / 2.1 | 180 | 0.36 | 51 |
| 25 | 1 | -16 | 25.4 | 32.6 | 200 / 1.4 | 250 | 0.55 | 51 |
- Working pressure reduces with size; the 350 psi figure must not be applied to all bores. Both psi and MPa figures are retained as printed. Burst pressure and vacuum reference basis: confirm for selected configuration.
Typical applications
- Selected low-pressure utility air and water services
- Fluid-transfer assemblies following a chemistry and temperature review
- Industrial service lines using a verified push-on fitting system
Technical selection
Define the complete operating envelope
Provide flow, coolant chemistry and concentration, minimum and maximum fluid temperatures, steady pressure, pressure transients, bore, ports, quantity and installation drawings. The lowest-rated component governs the assembled loop.
Keep the material families separate
Confirm the inner-tube compound and system cleanliness requirements before considering coolant service. A multipurpose hose is not automatically a data-centre coolant hose or an EPDM replacement.
Installation and handling
Installation guidance — not an additional rating
Isolate the loop, allow it to cool and follow the selected assembly's pressure-relief and connection procedure. Do not assume a coupling can be disconnected or connected against trapped pressure without a configuration-specific instruction.
Routing and mechanical support
Support hose and manifold loads independently. Avoid torsion, side loading, sharp edges and bends immediately behind a ferrule. Respect the selected hose's minimum bend radius and the connector's permitted misalignment.
Inspection and maintenance
Check seals, locking features, hose cover, fittings and signs of fluid loss before service. Flush and commission to the system's cleanliness and leak-test procedure; obtain the selected configuration's maintenance and replacement guidance.
Options and configurations
Colour and termination options
Choose black, blue, red, green, grey, white or yellow; the 1-inch size is limited to black and grey. Use the matching push-on fitting and approved assembly procedure; do not assume every fitting can be used without a clamp.
Frequently asked questions
Can this replace an EPDM cooling hose?
Not by default. Tube compound, fluid compatibility, cleanliness, temperature, fittings and assembly approval must be checked. It is intentionally separated from the dedicated cooling-hose constructions.
Are these values guaranteed for every assembly?
No. Tables preserve the stated size-specific figures and qualifications. Ratings for a finished hose assembly, coolant mixture and temperature must be confirmed; a minimum burst pressure is not an allowable working pressure.
What is needed for a selection enquiry?
Send flow, coolant chemistry and concentration, operating temperatures, pressure and transients, bore, ports, mating interface, quantity and drawings. Include an existing mating half when interface identification is uncertain.
Product views. Final configuration may vary.
Send your connection requirements
Email the following so our engineers can review a suitable coupling or hose configuration:
- Flow rate and allowable pressure drop
- Coolant chemistry and glycol concentration
- Operating and ambient temperatures
- Operating pressure
- Bore or hose inner diameter
- Port and thread types
- Mating interface or existing coupling
- Quantity
- Drawings or rack and manifold layout