Coolant Distribution Unit LL-120
A 4U, 19-inch liquid-to-liquid CDU for high-density server cooling with up to 120kW published cooling capacity.

The LL-120 is a rack-mounted heat-exchange unit designed for demanding data-centre installation environments and high-density liquid-cooled servers. Liquid-to-liquid cooling transfers heat from the secondary server-coolant circuit to the primary cooling-tower circuit. The unit supports ASHRAE W1–W4 coolant conditions and can manage 120+kW heat loads, supporting lower operating costs and improved CPU/GPU efficiency.
Key features
High-density cooling and redundancy
The 4U rack format provides 70kW/120kW heat removal. A stainless-steel heat exchanger, redundant power supplies and redundant pumps support reliable operation.
Visual monitoring
A 7-inch touchscreen and Web visualisation provide real-time monitoring of power consumption and core temperature loads. Flashing alarm indicators flag abnormal conditions.
Flexible deployment
Network and hotspot operating modes support deployment. Clamp fittings or optional quick-connect couplings accommodate different installation conditions.
Specifications
| Parameter | Value |
|---|---|
| Height | 4U |
| Dimensions | 175 × 446 × 870mm (H × W × D) |
| Cooling capacity | 120kW @ 10°C; 70kW @ 4°C |
| Flow | Primary side: 100LPM; Secondary side: >65LPM @ 1bar, >80LPM @ 0.5bar |
| Maximum operating pressure | Primary side: 8bar; Secondary side: 2.5bar internal pressure relief, 3bar external pressure relief |
| Rated inlet coolant temperature | Primary side: 17°C; secondary side: 27°C @ 120kW; Primary side: 35°C; secondary side: 39°C @ 70kW |
| Rated return coolant temperature | Primary side: 36°C; secondary side: 55°C @ 120kW; Primary side: 46°C; secondary side: 55°C @ 70kW |
| Default medium | Primary side: 40% EG; Secondary side: 25% PG |
| Pump drive configuration | Dual-pump variable-frequency control |
| Power consumption | 400W under redundant operation; 800W at maximum operating conditions |
| Power specification | 100–240VAC, 50–60Hz, single phase, N+1 redundancy |
| External connections | φ50.5 clamp connections (optional quick-connect couplings) |
| Power connectors | 2 × C14 |
| Communication interfaces | RS485, RJ45 |
| Communication protocols | Modbus-RTU & Modbus-TCP (extended support for SNMP, MQTT, HTTP) |
| Refill connection | CB05 female quick-connect |
| Noise level @ 3m | <47dB(A) |
Applications
- Liquid-cooled data centres
- Liquid-cooling research laboratories
- Data-centre upgrades and retrofits
Contact our team for LL-120 availability and project requirements.
Request product information