Anti-Static Copper-Wire EPDM Cooling Hose
Wrapped-cover EPDM cooling hose with textile reinforcement and anti-static copper-wire layers for applications requiring an explicitly reviewed electrical path.

Compare bore, outside diameter, reinforcement, bending clearance and mass when planning the coolant route. Select end fittings and assembly methods for this construction rather than substituting another hose with the same nominal bore.
Product views
Copper-wire reinforced hose construction
Technical overview
Construction and reinforcement
A smooth black EPDM tube is reinforced with two high-strength synthetic-fibre layers and two anti-static copper-wire layers beneath an abrasion-, ozone- and weather-resistant EPDM cover. The reinforcement is copper wire, not the steel helix used in the separate steel-helix family.
Fluid and temperature considerations
The documented application is water-based data-centre and electronics cooling. Verify glycol chemistry, concentration, inhibitors, cleaning fluids, electrical requirements and all wetted components. Do not assume EPDM is suitable for fuels or mineral oils.
Cover flammability requirements
For a UL94 V-0 cover requirement, confirm the test edition and material report for the selected hose. No UL listing or fire rating for the completed assembly is claimed.
Electrical requirements
Confirm the applicable EN12115 edition, electrical-resistance limit, test evidence and assembly continuity. The anti-static description alone does not establish a grounding arrangement or hazardous-area suitability.
Specifications
| Size (in) | ID (mm) | OD (in / mm) | Working pressure (psi / bar) | Minimum burst pressure (psi / bar) | Minimum bend radius (in / mm) | Mass (kg/m) |
|---|---|---|---|---|---|---|
| 1 | 25.4 | 1.5 / 37.0 | 232 / 16 | 928 / 64 | 5.9 / 150 | 0.63 |
| 1 1/4 | 32.0 | 1.7 / 44.0 | 232 / 16 | 928 / 64 | 6.9 / 175 | 0.85 |
| 1 1/2 | 38.0 | 2.0 / 51.0 | 232 / 16 | 928 / 64 | 8.8 / 225 | 0.97 |
| 2 | 51.0 | 2.6 / 67.0 | 232 / 16 | 928 / 64 | 10.8 / 275 | 1.61 |
| 2 1/2 | 63.5 | 3.1 / 79.0 | 232 / 16 | 928 / 64 | 11.8 / 300 | 2.02 |
| 3 | 76.0 | 3.6 / 92.0 | 232 / 16 | 928 / 64 | 13.8 / 350 | 2.72 |
- Both unit columns are transcribed as printed; nominal inch sizes and rounded metric equivalents are not silently recalculated. Minimum burst pressure is not working pressure.
- The stated hose temperature range is −40°C to +140°C. No pressure-temperature derating curve or completed-assembly rating is supplied; confirm for selected coolant, end fitting and temperature.
- Wrapped cover only; no smooth-cover option is listed.
Typical applications
- Data-centre rack and manifold coolant connections
- GPU and AI server cooling loops
- CDU-to-manifold distribution and HPC infrastructure
- Industrial electronics and energy-storage thermal management, subject to application review
Technical selection
Define the complete operating envelope
Provide flow, coolant chemistry and concentration, minimum and maximum fluid temperatures, steady pressure, pressure transients, bore, ports, quantity and installation drawings. The lowest-rated component governs the assembled loop.
Select reinforcement and bending behaviour
Compare actual ID, OD, minimum bend radius, reinforcement and mass. Textile, anti-static copper-wire, steel-helix and corrugated constructions are not interchangeable; reserve clearance for fittings and the completed routing envelope.
Installation and handling
Installation guidance — not an additional rating
Isolate the loop, allow it to cool and follow the selected assembly's pressure-relief and connection procedure. Do not assume a coupling can be disconnected or connected against trapped pressure without a configuration-specific instruction.
Routing and mechanical support
Support hose and manifold loads independently. Avoid torsion, side loading, sharp edges and bends immediately behind a ferrule. Respect the selected hose's minimum bend radius and the connector's permitted misalignment.
Inspection and maintenance
Check seals, locking features, hose cover, fittings and signs of fluid loss before service. Flush and commission to the system's cleanliness and leak-test procedure; obtain the selected configuration's maintenance and replacement guidance.
Options and configurations
Cover colours and identification
Black, red and blue covers are described. Confirm the chosen colour, surface finish, cleanliness specification and end-fitting assembly rather than transferring an option from another construction.
Assembly and documentation
Specify cut length, fitting materials, termination method, bend orientation, coolant and test requirements. Request material and test documentation for the actual hose assembly; component data alone does not rate the finished assembly.
Frequently asked questions
Can the 1:1 bend-radius ratio be used for this hose?
Only the corrugated large-bore construction has documented 1:1 minimum-bend-radius-to-ID entries. Other constructions must use their own row-specific values.
Are these values guaranteed for every assembly?
No. Tables preserve the stated size-specific figures and qualifications. Ratings for a finished hose assembly, coolant mixture and temperature must be confirmed; a minimum burst pressure is not an allowable working pressure.
What is needed for a selection enquiry?
Send flow, coolant chemistry and concentration, operating temperatures, pressure and transients, bore, ports, mating interface, quantity and drawings. Include an existing mating half when interface identification is uncertain.
Product views. Final configuration may vary.
Send your connection requirements
Email the following so our engineers can review a suitable coupling or hose configuration:
- Flow rate and allowable pressure drop
- Coolant chemistry and glycol concentration
- Operating and ambient temperatures
- Operating pressure
- Bore or hose inner diameter
- Port and thread types
- Mating interface or existing coupling
- Quantity
- Drawings or rack and manifold layout

