Blind-Mate Quick-Disconnect Couplings
UQDB blind-mate connectors for guided rack insertion, with size-specific pressure ratings and a stated radial compensation allowance.

Specify bore, end connections, coolant and operating conditions, then compare the selected size's hydraulic data and mating geometry. Check connected and disconnected limits separately when planning maintenance.
Product views
Guided blind-mate connection components
Technical overview
Blind-mate construction
Stainless-steel bodies and EPDM seals support guided connection where access to the mating halves is limited. Radial compensation is ±1 mm; review guide geometry and mounting support for the selected rack.
Interface verification
Confirm the applicable OCP interface specification, revision and mating dimensions for the selected configuration. No OCP certification, OEM approval or universal interchangeability is claimed.
Specifications
| Variant | Body size (in) | Nominal flow diameter (mm) | Connected working pressure (bar / psi) | Disconnected socket working pressure (bar / psi) | Disconnected plug working pressure (bar / psi) | Connected minimum burst pressure (bar / psi) | Socket minimum burst pressure (bar / psi) | Plug minimum burst pressure (bar / psi) | Rated flow (L/min / gpm) | Cv | Air inclusion (maximum; unit unspecified) | Fluid loss (maximum; unit unspecified) | Misalignment (mm) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| UQDB 04 | 1/4 | 5.5 | 16 / 232 | 16 / 232 | 16 / 232 | 48 / 696 | 48 / 696 | 48 / 696 | 6.4 / 1.7 | 1.22 | 0.004 | 0.025 | 1 |
| UQDB 06 | 3/8 | 6.3 | 10 / 145 | 10 / 145 | 10 / 145 | 30 / 435 | 30 / 435 | 30 / 435 | 11.36 / 3 | 2.23 | 0.007 | 0.035 | 1 |
- Air-inclusion and fluid-loss units and test conditions require confirmation before comparing these values with another coupling.
- Numerical ratings are shown for 04 and 06. Confirm dimensions and ratings for 02 and 08; do not extend another size's pressure limit.
- No family-specific temperature range, temperature derating, insertion force, withdrawal force or quantified helium acceptance criterion is supplied for this family. Confirm for selected configuration.
Typical applications
- Data-centre rack and manifold coolant connections
- GPU and AI server cooling loops
- CDU-to-manifold distribution and HPC infrastructure
- Industrial electronics and energy-storage thermal management, subject to application review
Technical selection
Define the complete operating envelope
Provide flow, coolant chemistry and concentration, minimum and maximum fluid temperatures, steady pressure, pressure transients, bore, ports, quantity and installation drawings. The lowest-rated component governs the assembled loop.
Check the exact mating interface
Provide the mating-half drawing or an existing mating half. Compare engagement geometry, shut-off sequence, sealing lands, port thread and tolerance stack; a family name alone does not establish interchangeability.
Verify coolant and seal compatibility
Review EPDM, FKM and all wetted materials against the actual glycol type, concentration, inhibitors, cleaning chemicals and temperature. Material names alone do not guarantee compatibility or lifetime.
Installation and handling
Installation guidance — not an additional rating
Isolate the loop, allow it to cool and follow the selected assembly's pressure-relief and connection procedure. Do not assume a coupling can be disconnected or connected against trapped pressure without a configuration-specific instruction.
Routing and mechanical support
Support hose and manifold loads independently. Avoid torsion, side loading, sharp edges and bends immediately behind a ferrule. Respect the selected hose's minimum bend radius and the connector's permitted misalignment.
Inspection and maintenance
Check seals, locking features, hose cover, fittings and signs of fluid loss before service. Flush and commission to the system's cleanliness and leak-test procedure; obtain the selected configuration's maintenance and replacement guidance.
Options and configurations
Ports, seals and coding
Specify the required port standard, end orientation and supply/return identification. Confirm availability and seal selection for the exact size instead of extending options from another family.
Documentation and test evidence
Request a controlled drawing and configuration-specific pressure, leakage and material documentation. Published test statements are not independent certification or a substitute for system validation.
Frequently asked questions
Does a family name establish interchangeability?
No. Confirm mating dimensions, materials, seals, tolerances, pressures and operating conditions for both halves. Generic UQD or blind-mate nomenclature is not evidence of universal compatibility.
Are these values guaranteed for every assembly?
No. Tables preserve the stated size-specific figures and qualifications. Ratings for a finished hose assembly, coolant mixture and temperature must be confirmed; a minimum burst pressure is not an allowable working pressure.
What is needed for a selection enquiry?
Send flow, coolant chemistry and concentration, operating temperatures, pressure and transients, bore, ports, mating interface, quantity and drawings. Include an existing mating half when interface identification is uncertain.
Product views. Final configuration may vary.
Send your connection requirements
Email the following so our engineers can review a suitable coupling or hose configuration:
- Flow rate and allowable pressure drop
- Coolant chemistry and glycol concentration
- Operating and ambient temperatures
- Operating pressure
- Bore or hose inner diameter
- Port and thread types
- Mating interface or existing coupling
- Quantity
- Drawings or rack and manifold layout