Interlocking Dry-Disconnect Ball-Valve Couplings
Full-flow dry-disconnect ball-valve couplings with identical mating halves and a mechanical safety interlock for coolant distribution.

Specify bore, end connections, coolant and operating conditions, then compare the selected size's hydraulic data and mating geometry. Check connected and disconnected limits separately when planning maintenance.
Product views
Female-threaded connection configuration Sanitary-flange connection configuration Hose-barb connection configuration Male-threaded connection configuration Disconnected coupling half — mating-face view Disconnected coupling half — reverse view
Technical overview
Full-flow construction and mechanical interlock
A straight-through ball-valve passage is combined with symmetrical mating halves. The mechanical sequence is intended to keep the valves closed until fully coupled and to prevent uncoupling before shut-off. Treat dry-break and low-spill wording as design intent, not an unqualified zero-leak guarantee.
Materials and size-dependent options
Stainless-steel bodies are offered with standard EPDM or optional FKM seals. Confirm the stainless grade, seal compound and temperature limits separately for the selected 1-inch or 2-inch configuration.
Qualified mating-interface suitability
Suitable for Danfoss FD83-type coupling interfaces, subject to verification of the exact size, mating dimensions, seals and operating conditions.
Mating and interface verification checklist
Request a controlled drawing or supply an existing mating half. Verify nominal size; coupling engagement and lock geometry; dimensional datums and tolerances; connection and valve sequence; port thread or flange; wetted materials and seals; fluid chemistry and concentration; pressure, transients and temperature. This statement does not imply OEM approval, affiliation or certified compatibility.
Interface verification
Confirm the applicable OCP interface specification, revision and mating dimensions for the selected configuration. No OCP certification, OEM approval or universal interchangeability is claimed.
Specifications
| Size (in) | Connected working pressure (bar / psi) | Disconnected half A working pressure (bar / psi) | Disconnected half B working pressure (bar / psi) | Connected minimum burst pressure (bar / psi) | Disconnected half A minimum burst pressure (bar / psi) | Disconnected half B minimum burst pressure (bar / psi) | Rated flow (L/min / gpm) | Cv | Fluid loss (cc) |
|---|---|---|---|---|---|---|---|---|---|
| 1 | 10 / 150 | 10 / 150 | 10 / 150 | 20 / 300 | 20 / 300 | 20 / 300 | 189 / 50 | 30 | 5.0 |
| 2 | 10 / 150 | 10 / 150 | 10 / 150 | 20 / 300 | 20 / 300 | 20 / 300 | 800 / 211 | 127 | 12 |
- Fluid-loss figures are size-specific, not a zero-leakage guarantee. The flow curve uses water at 70°F; confirm the rated-flow pressure-drop condition.
- No family-specific temperature range, temperature derating, insertion force, withdrawal force or quantified helium acceptance criterion is supplied for this family. Confirm for selected configuration.
| Size (in) | Connection | Body size (mm) | A (mm / in) | B (mm / in) | Hex (mm / in) |
|---|---|---|---|---|---|
| 1 | Hose barb | 51.17 | 86.01 / 3.39 | 64.45 / 2.54 | — |
| 1 | Male threaded | 51.17 | 97.53 / 3.84 | 64.45 / 2.54 | 41 / 1.61 |
| 1 | Female threaded | 51.17 | 97.53 / 3.84 | 64.45 / 2.54 | 41 / 1.61 |
| 1 | Sanitary flange | 51.17 | 81.12 / 3.19 | 64.45 / 2.54 | — |
| 2 | Hose barb | 71.38 | 109 / 4.29 | 101 / 3.98 | — |
| 2 | Male threaded | 71.38 | 114.5 / 4.51 | 101 / 3.98 | 69.6 / 2.74 |
| 2 | Female threaded | 71.38 | 98.6 / 3.88 | 101 / 3.98 | 69.6 / 2.74 |
| 2 | Sanitary flange | 71.38 | 96.5 / 3.80 | 101 / 3.98 | — |
- A is the axial dimension and B the outside-diameter datum. Body size is a separate dimension, not flow bore. A dash means unlisted, not zero. Use a controlled mating drawing for interface design.
Typical applications
- Data-centre rack and manifold coolant connections
- GPU and AI server cooling loops
- CDU-to-manifold distribution and HPC infrastructure
- Industrial electronics and energy-storage thermal management, subject to application review
Technical selection
Define the complete operating envelope
Provide flow, coolant chemistry and concentration, minimum and maximum fluid temperatures, steady pressure, pressure transients, bore, ports, quantity and installation drawings. The lowest-rated component governs the assembled loop.
Check the exact mating interface
Provide the mating-half drawing or an existing mating half. Compare engagement geometry, shut-off sequence, sealing lands, port thread and tolerance stack; a family name alone does not establish interchangeability.
Verify coolant and seal compatibility
Review EPDM, FKM and all wetted materials against the actual glycol type, concentration, inhibitors, cleaning chemicals and temperature. Material names alone do not guarantee compatibility or lifetime.
Installation and handling
Installation guidance — not an additional rating
Isolate the loop, allow it to cool and follow the selected assembly's pressure-relief and connection procedure. Do not assume a coupling can be disconnected or connected against trapped pressure without a configuration-specific instruction.
Routing and mechanical support
Support hose and manifold loads independently. Avoid torsion, side loading, sharp edges and bends immediately behind a ferrule. Respect the selected hose's minimum bend radius and the connector's permitted misalignment.
Inspection and maintenance
Check seals, locking features, hose cover, fittings and signs of fluid loss before service. Flush and commission to the system's cleanliness and leak-test procedure; obtain the selected configuration's maintenance and replacement guidance.
Options and configurations
Connection options
Options include NPT and BSP threads, hose barbs and sanitary flanges, with custom ports subject to confirmation. Specify the exact thread, flange standard and application requirements.
Ports, seals and coding
Specify the required port standard, end orientation and supply/return identification. Confirm availability and seal selection for the exact size instead of extending options from another family.
Documentation and test evidence
Request a controlled drawing and configuration-specific pressure, leakage and material documentation. Published test statements are not independent certification or a substitute for system validation.
Frequently asked questions
Does a family name establish interchangeability?
No. Confirm mating dimensions, materials, seals, tolerances, pressures and operating conditions for both halves. Generic UQD or blind-mate nomenclature is not evidence of universal compatibility.
Are these values guaranteed for every assembly?
No. Tables preserve the stated size-specific figures and qualifications. Ratings for a finished hose assembly, coolant mixture and temperature must be confirmed; a minimum burst pressure is not an allowable working pressure.
What is needed for a selection enquiry?
Send flow, coolant chemistry and concentration, operating temperatures, pressure and transients, bore, ports, mating interface, quantity and drawings. Include an existing mating half when interface identification is uncertain.
Product views. Final configuration may vary.
Send your connection requirements
Email the following so our engineers can review a suitable coupling or hose configuration:
- Flow rate and allowable pressure drop
- Coolant chemistry and glycol concentration
- Operating and ambient temperatures
- Operating pressure
- Bore or hose inner diameter
- Port and thread types
- Mating interface or existing coupling
- Quantity
- Drawings or rack and manifold layout