Liquid Cooling Connections & Hoses

Self-Centering Blind-Mate Couplings

Floating blind-mate couplings for guided rack connections, with a 5 mm bore and configuration-specific alignment requirements.

Self-centering mounting-block configuration

Specify bore, end connections, coolant and operating conditions, then compare the selected size's hydraulic data and mating geometry. Check connected and disconnected limits separately when planning maintenance.

  • Self-centering mounting-block configuration
  • Floating blind-mate connection components

Technical overview

Floating alignment and flat-face shut-off

Stainless-steel bodies, EPDM seals and a floating mount assist blind alignment. Flat-face shut-off elements are designed for low-spill handling; red and blue identification distinguish supply and return.

Alignment limits

Alignment figures require confirmation against the selected mounting drawing. Do not use the unverified mounting-table entries below as installation allowances.

Interface verification

Confirm the applicable OCP interface specification, revision and mating dimensions for the selected configuration. No OCP certification, OEM approval or universal interchangeability is claimed.

Specifications

Self-centering hydraulic data
Bore (mm)Working pressure (bar / psi)Minimum burst pressure (bar / psi)Rated flow (L/min / gpm)Cv
52.4 / 3513.8 / 2006 / 1.61.04
  • For the 3 mm option, flow test conditions, connection forces and spill quantities: confirm for selected configuration.
Unresolved mounting-table entries
EntryPrinted value
Radial misalignment (mm; disputed)±5
Angular misalignment (degrees; disputed)±2.7
Socket torque (N/m; unit unverified)40 ±5
Plug torque (N/m; unit unverified)25 ±5
  • Torque units and the tightening procedure require confirmation. Do not use these entries as tightening instructions or assume interchangeability with another UQD interface.

Typical applications

  • Data-centre rack and manifold coolant connections
  • GPU and AI server cooling loops
  • CDU-to-manifold distribution and HPC infrastructure
  • Industrial electronics and energy-storage thermal management, subject to application review

Technical selection

Define the complete operating envelope

Provide flow, coolant chemistry and concentration, minimum and maximum fluid temperatures, steady pressure, pressure transients, bore, ports, quantity and installation drawings. The lowest-rated component governs the assembled loop.

Check the exact mating interface

Provide the mating-half drawing or an existing mating half. Compare engagement geometry, shut-off sequence, sealing lands, port thread and tolerance stack; a family name alone does not establish interchangeability.

Verify coolant and seal compatibility

Review EPDM, FKM and all wetted materials against the actual glycol type, concentration, inhibitors, cleaning chemicals and temperature. Material names alone do not guarantee compatibility or lifetime.

Installation and handling

Installation guidance — not an additional rating

Isolate the loop, allow it to cool and follow the selected assembly's pressure-relief and connection procedure. Do not assume a coupling can be disconnected or connected against trapped pressure without a configuration-specific instruction.

Routing and mechanical support

Support hose and manifold loads independently. Avoid torsion, side loading, sharp edges and bends immediately behind a ferrule. Respect the selected hose's minimum bend radius and the connector's permitted misalignment.

Inspection and maintenance

Check seals, locking features, hose cover, fittings and signs of fluid loss before service. Flush and commission to the system's cleanliness and leak-test procedure; obtain the selected configuration's maintenance and replacement guidance.

Options and configurations

Ports, seals and coding

Specify the required port standard, end orientation and supply/return identification. Confirm availability and seal selection for the exact size instead of extending options from another family.

Documentation and test evidence

Request a controlled drawing and configuration-specific pressure, leakage and material documentation. Published test statements are not independent certification or a substitute for system validation.

Frequently asked questions

Does a family name establish interchangeability?

No. Confirm mating dimensions, materials, seals, tolerances, pressures and operating conditions for both halves. Generic UQD or blind-mate nomenclature is not evidence of universal compatibility.

Are these values guaranteed for every assembly?

No. Tables preserve the stated size-specific figures and qualifications. Ratings for a finished hose assembly, coolant mixture and temperature must be confirmed; a minimum burst pressure is not an allowable working pressure.

What is needed for a selection enquiry?

Send flow, coolant chemistry and concentration, operating temperatures, pressure and transients, bore, ports, mating interface, quantity and drawings. Include an existing mating half when interface identification is uncertain.

Product views. Final configuration may vary.

Send your connection requirements

Email the following so our engineers can review a suitable coupling or hose configuration:

  • Flow rate and allowable pressure drop
  • Coolant chemistry and glycol concentration
  • Operating and ambient temperatures
  • Operating pressure
  • Bore or hose inner diameter
  • Port and thread types
  • Mating interface or existing coupling
  • Quantity
  • Drawings or rack and manifold layout
Request connection information