Coolant Distribution Units

Coolant Distribution Unit AL-16

A 6U air-to-liquid CDU rated at 16kW, with redundant pumps, touchscreen operation and TCP/Modbus monitoring.

Coolant Distribution Unit AL-16 — embodyne.ai

The AL-16 is a rack-mounted heat-exchange unit for ultra-high-density cold-plate liquid-cooled servers. Rated cooling capacity is 16kW. Clamp-style connections simplify installation, and redundant pumps support reliability and maintenance. The system manages and distributes cooling for liquid-cooled servers, with comprehensive real-time operating-parameter monitoring and TCP/Modbus communication.

Selection and project planning

Assess the AL-16 as a liquid-to-air cooling option in the context of the room that receives the rejected heat. The CDU's published capacity does not establish whether the room's air-conditioning system can carry the added load. Review the operating conditions, coolant flow, installation dimensions and available electrical supply. Compare the smaller AL models when evaluating space and load requirements, without assuming that different CDUs are interchangeable.

Key features

Intelligent flow control

Redundant pump motors use variable-speed control to adjust system flow in response to server load.

Real-time monitoring

Tracks exhaust-air temperature, supply-coolant temperature, supply and return pressure, and coolant flow.

Local operating display

A 7-inch touchscreen displays operating status, system alarms and self-test information and supports local operation.

Specifications

Technical specifications
ParameterValue
Height6U
Dimensions266.7 × 445 × 860mm (H × W × D)
Rated cooling capacity16kW at 25°C ambient temperature and 50% RH
Cooling mediumPrimary side: air; Secondary side: specialist coolant
FlowSecondary side: 24LPM
Operating pressure≤1.5bar
Rated outlet coolant temperatureSecondary side: 40°C
Airflow directionFront intake, rear exhaust
Pump drive configurationDual-pump control
Power consumption950W
Power specification2 × 1P 220V 50Hz/60Hz
External connections2″ clamp connections
Power connectors2 × C14
Communication interface1 × RJ45
Communication protocolsTCP/Modbus

Applications

  • Liquid-cooled data centres