Coolant Distribution Unit AL-16
A 6U air-to-liquid CDU rated at 16kW, with redundant pumps, touchscreen operation and TCP/Modbus monitoring.

The AL-16 is a rack-mounted heat-exchange unit for ultra-high-density cold-plate liquid-cooled servers. Rated cooling capacity is 16kW. Clamp-style connections simplify installation, and redundant pumps support reliability and maintenance. The system manages and distributes cooling for liquid-cooled servers, with comprehensive real-time operating-parameter monitoring and TCP/Modbus communication.
Key features
Intelligent flow control
Redundant pump motors use variable-speed control to adjust system flow in response to server load.
Real-time monitoring
Tracks exhaust-air temperature, supply-coolant temperature, supply and return pressure, and coolant flow.
Local operating display
A 7-inch touchscreen displays operating status, system alarms and self-test information and supports local operation.
Specifications
| Parameter | Value |
|---|---|
| Height | 6U |
| Dimensions | 266.7 × 445 × 860mm (H × W × D) |
| Rated cooling capacity | 16kW at 25°C ambient temperature and 50% RH |
| Cooling medium | Primary side: air; Secondary side: specialist coolant |
| Flow | Secondary side: 24LPM |
| Operating pressure | ≤1.5bar |
| Rated outlet coolant temperature | Secondary side: 40°C |
| Airflow direction | Front intake, rear exhaust |
| Pump drive configuration | Dual-pump control |
| Power consumption | 950W |
| Power specification | 2 × 1P 220V 50Hz/60Hz |
| External connections | 2″ clamp connections |
| Power connectors | 2 × C14 |
| Communication interface | 1 × RJ45 |
| Communication protocols | TCP/Modbus |
Applications
- Liquid-cooled data centres