Coolant Distribution Unit LL-120
- Height
- 4U
- Dimensions
- 175 × 446 × 870mm (H × W × D)
- Cooling capacity
- 120kW @ 10°C; 70kW @ 4°C
A 4U, 35kW liquid-to-liquid CDU with redundant pumps and integrated PLC monitoring.

The LL-35 is a rack-mounted heat-exchange unit for ultra-high-density cold-plate liquid-cooled servers. Its rated cooling capacity is 35kW. Clamp connections simplify installation, while redundant pumps support reliability, replacement and maintenance. The unit exchanges heat between the outdoor-side cooling-water circuit and the secondary coolant circuit and manages and distributes cooling capacity.
The LL-35 is a liquid-to-liquid option: planning therefore starts with both the facility-water circuit and the server-side circuit. Check the published inlet and outlet conditions against the intended installation rather than comparing CDUs only by rated capacity. Review flow, differential pressure, coolant selection and clamp connections with the rack designer. Confirm pump redundancy, maintenance access and the required PLC alarm integration during the technical assessment.
Redundant pump motors use variable-speed control to adjust system flow in response to server load.
PLC control integrates monitoring of temperature, flow, pressure, leakage and liquid level.
A three-level alarm mechanism helps operations staff locate system abnormalities quickly.
| Parameter | Value |
|---|---|
| Height | 4U |
| Dimensions | 171.5 × 445 × 898mm (H × W × D) |
| Rated cooling capacity | 35kW |
| Flow | Primary side: ≥3 m³/h; Secondary side: 3 m³/h |
| Maximum rated output differential pressure | Secondary side: ≥14.06/1.0 bar |
| Rated inlet coolant temperature | Primary side: 35°C; Secondary side: 50°C |
| Rated outlet coolant temperature | Primary side: 45°C; Secondary side: 40°C |
| Pump drive configuration | Dual-pump variable-frequency control |
| Maximum power consumption | 300W |
| Power specification | AC220V 50Hz ±10% |
| External connections | φ50.5 clamp connections |
| Power connector | C14 |
| Communication interfaces | 2 × RS485 |
| Communication protocols | Modbus RTU & Modbus TCP/IP |
| Refill connection | HND06 male quick-connect |
| Noise level | 72dB(A) |
The secondary-side differential-pressure notation is reproduced as published. No primary-side differential-pressure value is specified.
These published details support comparison and system planning; links do not confirm compatibility. Review each model's complete specifications before configuration.