Coolant Distribution Units

Coolant Distribution Unit LL-35

A 4U, 35kW liquid-to-liquid CDU with redundant pumps and integrated PLC monitoring.

Coolant Distribution Unit LL-35 — embodyne.ai

The LL-35 is a rack-mounted heat-exchange unit for ultra-high-density cold-plate liquid-cooled servers. Its rated cooling capacity is 35kW. Clamp connections simplify installation, while redundant pumps support reliability, replacement and maintenance. The unit exchanges heat between the outdoor-side cooling-water circuit and the secondary coolant circuit and manages and distributes cooling capacity.

Selection and project planning

The LL-35 is a liquid-to-liquid option: planning therefore starts with both the facility-water circuit and the server-side circuit. Check the published inlet and outlet conditions against the intended installation rather than comparing CDUs only by rated capacity. Review flow, differential pressure, coolant selection and clamp connections with the rack designer. Confirm pump redundancy, maintenance access and the required PLC alarm integration during the technical assessment.

Key features

Intelligent flow control

Redundant pump motors use variable-speed control to adjust system flow in response to server load.

System monitoring

PLC control integrates monitoring of temperature, flow, pressure, leakage and liquid level.

Intelligent alarms

A three-level alarm mechanism helps operations staff locate system abnormalities quickly.

Specifications

Technical specifications
ParameterValue
Height4U
Dimensions171.5 × 445 × 898mm (H × W × D)
Rated cooling capacity35kW
FlowPrimary side: ≥3 m³/h; Secondary side: 3 m³/h
Maximum rated output differential pressureSecondary side: ≥14.06/1.0 bar
Rated inlet coolant temperaturePrimary side: 35°C; Secondary side: 50°C
Rated outlet coolant temperaturePrimary side: 45°C; Secondary side: 40°C
Pump drive configurationDual-pump variable-frequency control
Maximum power consumption300W
Power specificationAC220V 50Hz ±10%
External connectionsφ50.5 clamp connections
Power connectorC14
Communication interfaces2 × RS485
Communication protocolsModbus RTU & Modbus TCP/IP
Refill connectionHND06 male quick-connect
Noise level72dB(A)

The secondary-side differential-pressure notation is reproduced as published. No primary-side differential-pressure value is specified.

Applications

  • Liquid-cooled data centres

Compare related models

These published details support comparison and system planning; links do not confirm compatibility. Review each model's complete specifications before configuration.

Contact our team for LL-35 availability and project requirements.