Coolant Distribution Unit LL-120
- Height
- 4U
- Dimensions
- 175 × 446 × 870mm (H × W × D)
- Cooling capacity
- 120kW @ 10°C; 70kW @ 4°C
A 4U, 6kW air-to-liquid CDU with redundant variable-speed pumps and PLC-based monitoring.

The AL-6 is a rack-mounted heat-exchange unit for ultra-high-density cold-plate liquid-cooled servers. Its rated cooling capacity is 6kW. Clamp connections simplify installation, while redundant pumps support reliable operation and maintenance. The system manages server cooling and cooling-capacity distribution, with comprehensive real-time parameter monitoring. Redundant RS485 and RJ45 communication interfaces use Modbus RTU and Modbus TCP/IP by default.
The AL-6 should be assessed against the actual coolant circuit and room environment, not chosen from its model name alone. Review published cooling capacity, flow, temperature conditions and connections alongside the server heat load. Account for the heat discharged into the room and the space needed for access and maintenance. Establish the power supply, monitoring requirements and site constraints before comparing it with larger liquid-to-air alternatives.
Redundant pump motors use variable-speed control to adjust system flow in response to server load.
PLC control integrates monitoring of temperature, flow, pressure, leakage and liquid level.
A three-level alarm mechanism helps operations staff locate system abnormalities quickly.
| Parameter | Value |
|---|---|
| Height | 4U |
| Dimensions | 177 × 481 × 982mm (H × W × D) |
| Rated cooling capacity | 6kW |
| Cooling medium | Primary side: air; Secondary side: specialist coolant |
| Flow | Primary side: 500 m³/h; Secondary side: 0.36 m³/h |
| Maximum rated output differential pressure | Secondary side: ≥1.0bar |
| Rated inlet temperature | Primary side: 25°C; Secondary side: 54.8°C |
| Rated outlet temperature | Primary side: 47°C; Secondary side: 40°C |
| Airflow direction | Front intake, rear exhaust |
| Pump drive configuration | Dual-pump variable-frequency control |
| Maximum power consumption | 300W |
| Power specification | 2 × 1P 220V 50Hz/60Hz |
| External connections | 1″ clamp connections |
| Power connectors | 2 × C14 |
| Communication interfaces | 2 × RS485 & 2 × RJ45 |
| Communication protocols | Modbus RTU & Modbus TCP/IP |
| Refill connection | UQD04 male connection |
| Noise level | 85dB(A) |
These published details support comparison and system planning; links do not confirm compatibility. Review each model's complete specifications before configuration.
Contact our team for AL-6 availability and project requirements.
Request product information